
|
|
Vital Signs
Project: Waverley Mansion
(Background) (Methodology)
(Building Results) (Model Results) (Conclusion) (References).
Temperature readings were taken on and between all floors every 30 minutes from 12:30 P.M. to 4:30 P.M. The average outside temperature was measured to be 65.8 deg F. The average temperatures vertically through the atrium are shown below.
Results from the air motion testing are provided in the table below and in Figure 11 below. Figure 11 emphasizes the results of condition three because it as the test to which the most time was devoted. The results are based on observation, not measurements. The table and figure provide the best average results; i.e. a pinwheel said to have spun continuously might only have spun 90% of the testing time. The colors used in Figure 11 do not correspond to actual rotational speeds of the pinwheels; instead, they show how pinwheel rotation compared from floor to floor and test to test. The yellow color can best be described as representing the amount of air flow past a person walking at a moderate pace on a still day. Pinwheel activity labeled as green is shown in Figure 10.
Conclusions The temperature data shows that hot air is rising in the 52 foot tall atrium space. Between the second and third floors, the temperature measurements rose and then fell again. This contradicts what was expected, but does not invalidate the data. The most likely cause of this "hot spot" is the electric light which hangs in middle of the atrium at the second floor level (Fig.12). The average relative humidity indoors and outdoors are almost the same. At 1:00 P.M., relative humidity outside equaled relative humidity inside. By 4:00 P.M, humidity inside was 1% less than humidity outside. This suggests that the increased ventilation somehow reduced the amount of moisture within the house. The air motion tests conducted under conditions one, two, and four yielded expected results. When there were no openings in the buiding's envelope, there was no air movement. When windows and doors were opened at the top or bottom, the most motion occurred nearest the opening. What was not expected was the slow air movement on the third floor during condition three testing. In fact, if the air was moving vertically due to thermal buoyancy, as was hypothesized, there should be more activity on the third floor because there were no openings to outside through which it could escape. Based on the results of all four test conditions, it was concluded that cross ventilation played a larger roll in passively cooling Waverley than did stack effect. |
|||||||||||||||||||||||||||||||||||||||||
Comments to
author: vitalsigns@ All contents copyright (C) 1998. Vital Signs Project. All rights reserved. Created: 04/08/97 |
|
|||||||||||||||||||||||||||||||||||||||||